Jacketed Metallic Conduits

Page Contents


Type LT

A general purpose flexible liquidtight steel conduit designed for a variety of installations requiring motion, vibration and bending. It offers good mechanical and moisture protection to enclosed conductors.

 

Construction

The flexible inner core is made from a spiral wound strip of electro-galvanized steel. The 1/4 through 1-1/4 inch trade sizes are squarelock formed and, with the exception of the 1/4 inch size, contain a nylon cord packing within the convolutions.

The larger sizes are constructed with a fully interlocked strip for added strength and to prevent unraveling.

A flexible yet durable PVC jacket is extruded over this core creating a liquidtight conduit resistant to most oils, acids and vapors present in industrial environments.

 

Working Temperatures:

-20 C to 80 C

JIC-manufactured in accordance with the dimensions and specifications as outlined by the Joint Industrial Council Standard for Mass Production Equipment and Machine Tools.

 

Applications:

This conduit is used extensively in the Machine Tool and other Industrial Environments where flexibility is necessary for installation, maintenance or where vibration and movement must be absorbed. The inherent Sunlight Resistance of PVC enables this pro duct to be used in outdoor applications. Compatible with Standard Liquidtight Connectors. The construction of this conduit conforms to, and is suitable for use with Sections 16 & 17.7 of the Electrical Standard for Industrial Machinery (ANSI/NFPA-79).

 

Standard Colors:

Machine tool Gray and Black. Other colors available upon request.

Page Contents


 

Type LOR

This product is offered as a non-UL oil resistant conduit that incorporates a high quality PVC jacket.

 

Applications:

The LOR is ideally used in situations where a UL listing or CSA certification is not a factor but where a flexible conduit must withstand exposure to many harsh chemicals, oils, UV, etc. This conduit conforms to Section 17.7 of the Electrical Standard  for Industrial Machinery (ANSI/NFPA-79). Compatible with Standard Liquidtight Connectors.

 

Working Temperatures:

-20 C to 80 C

 

Standard Colors:

Machine Tool Gray and Black. Other colors available upon request.

 

Note:

A UL listed version is available. Consult factory for type LA/LOR.

Page Contents


 

Type EF

This flexible liquidtight conduit is a competitive grade version of our type LT. It conforms to both the JIC standards for dimensions and general construction, and to Section 17.7 of the Electrical Standard for Industrial Machinery. (ANSI/NFPA-79)

 

Construction:

The flexible inner core is constructed from a helically formed strip of corrosion resistant steel. A liquidtight PVC jacket is then extruded over the core.

 

Working Temperature:

-20 C to 80 C

 

Applications:

General installations requiring some movement and protection for contained conductors. Forms a liquidtight system when installed with the standard connectors for use indoors or out.

Standard Color:

Machine Tool Gray

Page Contents


 

Type LA

A flexible liquidtight steel conduit which is both listed by Underwriters Laboratories Inc. and Certified by Canadian Standards Association. It offers outstanding protection against wet, oily conditions and is permitted for use in exposed or concealed lo cations.

 

Construction:

The flexible inner core is made from a spiral wound strip of heavy gauge, corrosion resistant, hot-dipped galvanized steel. The 3/8 through 1-1/4 inch trade size are square lock formed and include an integral bonding strip of copper that is enclosed with in the convolutions throughout it's entire length. The 1-1/2 through 4 inch trade sizes are designed with a fully interlocked strip.

The liquidtight jacketing material is of a high quality, rugged, flame retardant flexible PVC compound which resists oils, mild acids and exposure to sunlight.

Working Temperatures:

-20 C to 60 C Intermitting to 90 C

UL Listed file # E29278. Conforms to Underwriters Laboratories Standard ANSI/UL-360 for Liquidtight Flexible Steel Conduit.
CSA Certified File LL # 18858. Conforms to CSA 22.2 No. 56 for use per the Canadian Electrical Code C22.1 Section 12-1300.

 

Applications:

This conduit is intended for installation in accordance with Article 351, part A of the NEC ® (ANSI/NFPA-70) and in sections 16 & 17.7 of the ANSI/NFPA-79 Standard for Industrial Machinery:

-Listed and marked for Direct Burial and in Poured Concrete.
-For containment of 600 volt and lower potential circuits
-Sunlight resistant
-Suitable as a grounding conductor when used for circuits rated up to 20A for the 3/8 & 1/2 inch trade sizes in lengths six feet of less per NEC® Article 351-9
-Installations in hazardous (classified) Locations:

Class I Div. 2 Article 501-4 (b)
Class II Div. 1 and 2 Article 502-4 (a)(2) and (b)(2)
Class III Div. 1 and 2 Article 503-3 (a) and (b)


-Use in Air Plenums Article 300-22
-Installed under raised floors in Data Processing Areas Articles 645-5 (d)(2)
-Electric Signs and Outline Lighting over 1000 volts Article 600-31 (a)

Standard Colors:

Machine tool Gray, and Black. Other colors available upon request. LA Blue is commonly used for computer room installations.

Page Contents


 

Type CSA

This flexible liquidtight steel conduit is Certified by the Canadian Standards Association. It's design and function is similar to that of type LA except that it cannot be used as a ground return path per the Canadian code and it offers a wider operating temperature range.

 

Construction:

The flexible inner core is made from a spiral wound strip of heavy gauge, corrosion resistant, hot-dipped galvanized steel. The 3/8 through 1-1/4 inch trade sizes are cord packed.

The durable PVC flame retardant jacket is designed for good flexibility and impact resistant characteristics at low temperatures.

 

Working Temperatures:

-40 C to 75 C

CSA- Certified File LL #18858. Conforms to CSA Standard C22.2 No. 56. Flame Test Rating FT-4 per CSA Standard C 22.2 No. 0.3.

 

Applications:

This conduit is intended for use according to the Canadian Electrical Code as described in clause 12-1300 for dry, damp or wet locations and in Hazardous Areas where flexibility is necessary per 18-202 (4)(b) and 18-302 (4) for both Class II and Class III locations.

 

Standard Color:

Black

Page Contents


 

Type HTA

This conduit uses the same inner flexible core as found in type LA conduits. The difference lies in the jacketing material's ability to withstand elevated temperatures.

 

Working Temperatures:

-17 C to 105 C/ Dry 60 C/Wet 70 C/Oil

UL-Listed File #E29278

-Conforms to Underwriters Laboratories Standard ANSI/UL-360 for Liquidtight Flexible Steel conduit.
-Conforms to the requirements of Section 16 & 17.7 of the ANSI/NFPA-79 Electrical Standard for Industrial Machinery.

 

Application:

It is designed to be used with high temperature machine tool wiring or in environments where a high ambient temperature might otherwise attack the flexibility characteristics of lower rated conduits.

 

Standard Color:

Machine Tool Gray

Page Contents


 

Type AT

A flexible steel conduit which uses a jacketing material specifically designed for hot or cold environments.

 

Construction:

The flexible inner steel core is identical to that found in type LT. The specially formulated PVC jacket remains flexible at very low temperatures, unlike most plasticized PVC. It also displays slower aging characteristics at elevated temperatures.

 

Working Temperatures:

-55 C to 105 C Intermitting to 120 C

 

Applications:

Type AT is well suited for exposure to extreme climatic conditions. It is also widely used on industrial process equipment such as Annealing ovens, Lumber kilns, Foundries, Refrigeration, etc. The construction of this conduit conforms to, and is suitabl e for use with Sections 16 & 17.7 of the Electrical Standard for Industrial Machinery (ANSI/NFPA-79). Uses standard liquidtight connectors.

 

Standard Colors:

Machine tool gray.

Page Contents


 

Type ATX

A conduit designed to withstand an extreme temperature range.

 

Construction:

Utilizes the flexibility of our standard LT core, coupled with the advantage of a Thermoplastic Rubber jacket that is virtually unaffected by temperature extremes and that contains no halogens. The material has a flammability rating of UL 94-HB.

 

Working Temperatures:

-60 C to 150 C Intermitting to 165 C

 

Applications:

Used in situations where concerns of resistance to temperature exposure exist. These include heavy outdoor equipment, boilers and furnaces, etc.

 

Standard Color:

Black

Page Contents


 

Type ALT

This version of Liquidtight Flexible Conduit is similar to our standard type LT but weighs considerably less due to the use of an aluminum inner core instead of steel.

 

Working Temperature:

-20 C to 80 C

 

Applications:

Type ALT is often used where weight or corrosive atmospheres are an issue. When comparing identical trade sizes, type ALT weighs approximately 37% less than type LT. Uses Standard Liquidtight Connectors.

 

Standard Colors:

Machine Tool Gray and Black. Other colors available upon request.

Page Contents


 

Type VJC

Vacuum jacketed steel conduit for high-flex installations.

 

Construction:

A unique vacuum extrusion process allows this product to have a thin PVC jacket which does not restrict the great flexibility characteristics of the inner core. The core material is the same as type SL. VJC is designed wit h dimensions that will accept standard liquidtight connectors.

 

Working Temperature:

-20C to 80C

 

Applications:

VJC is suitable for use in both static applications where a tight bend diameter is needed and in dynamic use such as machining centers and robotics. Conduits of the extra-flexible construction are permitted for use as described in Section 17.7.4 of the E lectrical Standard for Industrial Machinery (ANSI/NFPA-79). Consult factory for recommended fittings in situations requiring sealed connections.

 

Standard Color:

Black. Other colors available upon request.

Page Contents


 

Type CEA

This liquidtight flexible steel conduit is designed for applications where safety concerns exist regarding a material's reaction in a fire situation.

 

Construction:

The flexible inner core of this product is made from a galvanized steel strip. As in type LT, this core contains string packing between the helical convolutions in trade sizes 3/8" through 1-1/4". The specially formulated thermopl astic polyurethane jacket has excellent flame retardation and low smoke and toxicity generation characteristics. Acidic gases such as hydrogen chloride, hydrogen fluoride and hydrogen bromide are virtually eliminated as products of combustion.

 

Working Temperature:

-40 C to 80 C

 

Applications:

This product is ideally suited for installation in confined or enclosed areas where construction materials must have limited smoke, low flame spread and low toxic gas emissions in the event of fire. Such applications include mass transit vehicles where C EA is extensively used for wiring harnesses within and under passenger rail cars. Other applications include use in underground subway structures and tunnels.

 

Standard Colors:

Gray and Black. Other colors available upon request.

 

Note:

A UL Listed version is pending. Consult factory for availability of type ZHLA.

Page Contents


 

Type EMS

Electro-Magnetic Shielding conduit is designed for use where shielding from Electro-Magnetic and Radio Frequency Interference is of concern. (EMI & RFI)

Construction:

The construction of EMS includes a fully interlocked inner core made from a helically wound strip of half-hard gilding bronze. Over this, a durable, all temperature PVC jacket is extruded resulting in a weather proof sealed wiring raceway when coupled wi th standard liquidtight steel and fittings.

 

Working Temperatures:

-55 C to 105 C Intermitting to 120 C

 

Applications:

This conduit is used to protect sensitive electronic circuits such as communications, radar, data transmission and similar installations. EMS has been installed on naval vessels for shielding purposes. The shielding effectiveness ranges from 100 db @ 1 GHz to 124 db @ 1 MHz.

-PVC Jacket material offers excellent resistance to most Oils, Acids, Alkalies, Ozone and UV.
-Standard color Gray
-Compatible with standard liquidtight connectors.

Page Contents


 

 

Non-Jacketed Metallic Conduits

Page Contents


Type BR

This non-jacketed flexible steel conduit has many universal wiring applications. It is often referred to as "Greenfield" or "Reduced Wall Flex."

 

Construction:

Type BR is formed from a high corrosion resistant hot-dipped galvanized steel. It's profile and helical shape allow it to withstand impact and crushing forces.

UL-Listed File #E53253 (Sizes 3/8 through 3 inch) Conforms to Underwriters Laboratories Standard ANSI/UL-1 for Flexible Metal Conduit.

CSA-Certified File #LL18858 (3/8 inch size only) Conforms to CSA 22.2 No. 56 for use per the Canadian Electrical Code C22.1 Section 12-1000.

Meets Federal Specification WW-C-566c Type II.

 

Applications:

This conduit is intended for installation as a metal raceway for wires and cable in accordance with the NEC® (ANSI/NFPA-70) Article 350.

-Suitable as a grounding conductor when used for circuits rated up to 20A and in lengths less than six feet or less (Section 350-5)
-Wiring in Elevators, Hoistways and Escalators (Section 620-21).
-Use of 3/8 inch trade size (Section 350-3)

*Leads of Motors (Section 430-145 (b) )
*Listed Assemblies, Tap Conductors (Section 410-67 (c) )
*Manufactured Wiring Systems - (Section 604-6) (a) )
*Listed Wired Fixtures (Section 410-77 (c) )

-Suitable for use with listed connectors intended for "FMC" (Flexible Metal Conduit). Flexible metal conduit is also permitted for use on Industrial machinery where temperatures exceed the limits of liquidtight flexible conduit. (ANSI/NFPA-79) Section 16.3.4 (Exception) and Section 17.9.

Page Contents


 

Type ABR

This non-jacketed flexible aluminum conduit has many universal wiring applications. It is often referred to as "Greenfield" or "Reduced Wall Flex."

 

Construction:

Type ABR is formed using a high strength aluminum alloy strip. The result is a conduit with similar characteristics to those of type BR steel but at about 1/3 the weight.

UL- Listed File #E53253 (Sizes 3/8 through 3 inch) Conforms to Underwriters Laboratories Standard ANSI/UL-1 for Flexible Metal Conduit.

CSA- Certified File #LL18858 (3/8 inch size only) Conforms to CSA 22.2 No. 56 for use per the Canadian Electrical Code C22.1 Section 12-1000.

Meets Federal Specification WW-C-566c Type I

 

Applications:

This conduit is intended for installation as a metal raceway for wires and cable in accordance with the NEC® (ANSI/NFPA-70) Article 350.

-Suitable as a grounding conductor when used for circuits rated up to 20A and in lengths six feet or less. (Section 350-5)
-Wiring in Elevators, Hoistways and Escalators (Section 620-21)
-Use of 3/8 inch trade size (Section 350-3)

*Leads of Motors (Section 430-145 (b) )
*Listed Assemblies, Tap Conductors (Section 410-67) (c) )
*Manufactured Wiring Systems (Section 604-6 (c) )
*Listed Wire Fixtures (Section 410-77 (c) )

-Suitable for use with listed connectors intended for "FMC"- Flexible Metal Conduit.

Flexible metal conduit is also permitted for use on Industrial machinery where temperatures exceed the limits of liquidtight flexible conduit. (ANSI/NFPA-79) Section 16.3.4 (Exception) and Section 17.9.

Page Contents


 

Type USL

This extra-flexible steel conduit is recognized by UL and CSA for use within Listed and Certified assemblies.

 

Construction:

Helically formed from hot-dipped galvanized steel, type USL offers good corrosion resistance and provides excellent mechanical protection to enclosed circuits.

UL- Recognized File #E53253
CSA- Report #LO 4000-4875

 

Applications:

This product is intended as a factory installed component of various assemblies. Typical uses include: Modular office partitions, Showcase lighting, Range tops and other appliances.

Page Contents


 

Type SL

This "extra-flexible" product, available in the smaller diameters, is designed for tight-spot installation and where continuous flexing is required of a steel wound hose.

 

Construction:

Type SL is helically wound from a formed strip of Electro-Galvanized steel. It is sized to be used with a variety of set-screw and clamp type connectors.

 

Applications:

Offers good mechanical protection to wiring in a variety of O.E.M. applications.

Page Contents


 

Type UG

A fully-interlocked flexible steel conduit designed for high-strength in "tight-spot" installations.

 

Construction:

This conduit is manufactured from a bright tin plated steel strip which is fully interlocked at the edges to produce a strong, yet flexible product. The interlock feature does not allow the conduit to unravel if twisted and permits the conduit to retain it's shape when bent. This lightweight product is compatible with many set-screw and clamp type connectors.

 

Applications:

The bright appearance of the finished product lends itself to installations where the conduit may be visible after final assembly.

Page Contents


 

Type PF

Plen-Flex® is a smoketight, liquidtight Flexible Metallic Tubing and is listed for use in plenums and other air handling spaces. Often referred to as FMT.

 

Construction:

Plen-Flex® is constructed from steel strip which contains an extra coating of zinc galvanizing for added protection against corrosion. This strip is formed into a corrugated profile and is tightly interlocked to form a smoketight, airtight and liquid tight pliable tube which weighs about 40% less than FMC (Greenfield).

UL- Listed File #E80694
Approved for use by the city of Chicago.

 

Applications:

This tubing is used to wire drop-in lighting fixtures and other equipment found in plenum ceilings and other air handling areas. Because it is smoketight when installed with sealing fittings and gasketed junction boxes, it would prevent smoke and other p roducts of combustion from escaping out of the raceway and into air handling areas in the event of an electrical fire. There is also no plastic jacketing material which might give off toxic gases or burn. The fact that the system is liquidtight means th at it will not allow the entrance of moisture from sprinkler systems into it's interior. It is intended to be installed in accordance with Article 349 of the NEC® (ANSI/NFPA-70).

-Listed for containment of 1000 volts and lower potential circuits.
-For use in dry locations.
-In accessible locations when protected from physical damage or concealed, such as above suspended ceilings.
-In branch circuits.
-Listed for grounding per Article 250-91 (b) Exception No. 1.

Page Contents


 

 

Non-Metallic Conduits

Page Contents


Type LNM-P

This nonmetallic liquidtight conduit is ideally suited for continuous flexing situations. It is often specified in "Power Track" or cable carrier installations and on industrial robots. It does not contain a metal core which could fatigue from repeated flexing or vibration.

 

Construction Type A:

LNM-P is of the Layered, Type-A construction which incorporates a smooth seamless inner core of flexible PVC that is bonded to a covering of flexible PFC. Between these layers is a woven nylon mesh for added reinforcement. The PVC material is a high qua lity flame-retarded compound which resists oils, mild acids and exposure to sunlight.

 

Fittings:

Fittings for Layered Conduit are for that conduit only and are so identified by the marking "FNMC-A"

 

Working Temperatures:

-20C to 60C

UL- Listed File #E79308
-Conforms to Underwriters Laboratories Standard ANSI/UL 1660 type A

CSA- Certified File #LL18858
-Conforms to CSA 22.2 No. 227.2 type A

 

Standard Colors:

Safety Orange. Also available in Black and Gray.

 

Packaging:

-Coiled in Cartons or in random lengths on Non-Returnable Reels.

 

Applications:

Both types LNM-P and NM are intended for installation in accordance with Article 351, part B of the NEC® (ANSI/NFPA-70) for Flexible Liquidtight Nonmetallic Conduit.

-For containment of 600 volt and lower potential circuits.
-Listed and Marked for Outdoor use.
-Installations in hazardous (classified) Locations:

Class I Div. 2 Article 501-4 (b)
Class II Div. 1 and 2 Article 502-4 (a)(2) and (b)(2)
Class III Div. 1 and 2 Article 503-3 (a) and (b)

-Electric Signs and Outline Lighting over 1000 volts Article 600-31 (a)
-Wiring methods for pools and spas article 680

Conforms to the requirements of Section 17.8 of the Electrical Standard for Industrial Machinery.

Page Contents


 

Type NM

A general purpose nonmetallic liquidtight conduit offers excellent protection to wiring from Abrasion, Sunlight, Mild Acids, Alkaline and Oils. Often used for air conditioning hook-ups and other outdoor applications.

 

Construction Type B:

NM is of the helically wound Integral Type B construction. It contains a spiral of rigid PVC reinforcement embedded within the flexible PVC wall.

 

Fittings:

Suitable for use with nonmetallic fittings marked for FNMC-B or with standard metal liquidtight fittings.

 

Working Temperatures:

-20C to 80C Dry, 60C Wet, 70C Oil

UL- Listed File #E79308 Conforms to Underwriters Laboratories Standard
-ANSI/UL 1660 type B
-The 3/8 through 1-1/4 inch trade sizes are listed and marked for Direct Burial and in poured Concrete.

CSA- Certified File #LL18858 Conforms to CSA 22.2 No. 227.2 type B

 

Applications:

Both types LNM-P and NM are intended for installation in accordance with Article 351, part B of the NEC® (ANSI/NFPA-70) for Flexible Liquidtight Nonmetallic Conduit.

-For containment of 600 volt and lower potential circuits.
-Listed and Marked for Outdoor use.
-Installations in hazardous (classified) Locations:

Class I Div. 2 Article 501-4 (b)
Class II Div. 1 and 2 Article 502-4 (a)(2) and (b)(2)
Class III Div. 1 and 2 Article 503-3 (a) and (b)

-Electric Signs and Outline Lighting over 1000 volts Article 600-31 (a)
-Wiring methods for pools and spas article 680

Conforms to the requirements of Section 17.8 of the Electrical Standard for Industrial Machinery.

 

Standard Colors:

Machine tool Gray and Black

Page Contents


 

Type CL-standard weight

Standard weight. Provides the best mechanical strength and protection of the Corrlok conduits.

 

The Corrlok/PMAFIX System:

The Corrlok System offers designers and electricians many advantages over numerous other wiring products. It provides a very light weight, liquidtight, flexible raceway resistant to abrasion, sunlight, temperature extremes and many common chemicals. The specially formulated nylon compounds are self extinguishing and release no halogens or corrosive gases in fire situations.

 

Applications:

Corrlok conduits are defined in the National Electrical Code (ANSI/NFPA-70) under article 351-22 (3) for Liquidtight Flexible Nonmetallic Conduits. It's design is also referred to as type C. The Corrlok System is well suited for many electrical installa tions such as Industrial Control Equipment, Machine Tools and Plastic Molding/Extrusion machinery. Also used for wiring Printing Presses, Textile Machinery and Medical Equipment. The system also lends itself quite well to non-electrical applications suc h as protecting air-logic circuitry and Fiber Optics. The conduits can be extruded in other colors to differentiate between Electrical circuits and Fiber Optics.

Because the materials used are non-toxic and self extinguishing, Corrlok is a proven choice for situations where the potential for fire in confined, inhabited areas is a concern. Passenger rail vehicles are just one of the many such examples.

 

Construction:

Conduits of the Corrlok System are manufactured in a continuous extrusion/corrugation process which produces a flexible seamless tube with annular corrugations. The corrugations are what gives the conduit it's strong crush and impact resistance and excel lent flexibility properties. The internal corrugations are well rounded which facilitates easy wire insertion.

 

Material:

Halogen Free Nylon 6

 

Working Temperature:

-40C to 105C Intermitting to 150C

Standard Color:

Black. Other colors available upon request.

UL Recognized Component File #E80294 (VOH) For Electrical Machine Installations 600 V, 105C, Vertical Flame, Liquidtight, UV, and Impact Tested.

 

Fitting Pull-Out:

150 lbs. (1/2" and larger). To be used only with PMAFIX connectors of the Corrlok System.

Page Contents


 

Type CLL-light weight

This light weight version provides many of the same qualities of type CL but with improved flexibility.

 

The Corrlok/PMAFIX System:

The Corrlok System offers designers and electricians many advantages over numerous other wiring products. It provides a very light weight, liquidtight, flexible raceway resistant to abrasion, sunlight, temperature extremes and many common chemicals. The specially formulated nylon compounds are self extinguishing and release no halogens or corrosive gases in fire situations.

 

Applications:

Corrlok conduits are defined in the National Electrical Code (ANSI/NFPA-70) under article 351-22 (3) for Liquidtight Flexible Nonmetallic Conduits. It's design is also referred to as type C. The Corrlok System is well suited for many electrical installa tions such as Industrial Control Equipment, Machine Tools and Plastic Molding/Extrusion machinery. Also used for wiring Printing Presses, Textile Machinery and Medical Equipment. The system also lends itself quite well to non-electrical applications suc h as protecting air-logic circuitry and Fiber Optics. The conduits can be extruded in other colors to differentiate between Electrical circuits and Fiber Optics.

Because the materials used are non-toxic and self extinguishing, Corrlok is a proven choice for situations where the potential for fire in confined, inhabited areas is a concern. Passenger rail vehicles are just one of the many such examples.

 

Construction:

Conduits of the Corrlok System are manufactured in a continuous extrusion/corrugation process which produces a flexible seamless tube with annular corrugations. The corrugations are what gives the conduit it's strong crush and impact resistance and excel lent flexibility properties. The internal corrugations are well rounded which facilitates easy wire insertion.

 

Material:

Halogen Free Nylon 6

 

Working Temperature:

-40C to 105C Intermitting to 150C

 

Standard Color:

Black. Other colors available upon request.

UL Recognized Component File #E80294 (VOS) For Electrical Machine Installations 600 V, 105C, Vertical Flame, Liquidtight, UV, and Impact Tested.

 

Fitting Pull-Out:

40 lbs. To be used only with PMAFIX connectors of the Corrlok System.

Page Contents


 

Type CCG-commercial grade

This commercial grade product is exceptionally light weight and provides a cost effective alternative.

 

The Corrlok/PMAFIX System:

The Corrlok System offers designers and electricians many advantages over numerous other wiring products. It provides a very light weight, liquidtight, flexible raceway resistant to abrasion, sunlight, temperature extremes and many common chemicals. The specially formulated nylon compounds are self extinguishing and release no halogens or corrosive gases in fire situations.

 

Applications:

Corrlok conduits are defined in the National Electrical Code (ANSI/NFPA-70) under article 351-22 (3) for Liquidtight Flexible Nonmetallic Conduits. It's design is also referred to as type C. The Corrlok System is well suited for many electrical installa tions such as Industrial Control Equipment, Machine Tools and Plastic Molding/Extrusion machinery. Also used for wiring Printing Presses, Textile Machinery and Medical Equipment. The system also lends itself quite well to non-electrical applications suc h as protecting air-logic circuitry and Fiber Optics. The conduits can be extruded in other colors to differentiate between Electrical circuits and Fiber Optics.

Because the materials used are non-toxic and self extinguishing, Corrlok is a proven choice for situations where the potential for fire in confined, inhabited areas is a concern. Passenger rail vehicles are just one of the many such examples.

 

Construction:

Conduits of the Corrlok System are manufactured in a continuous extrusion/corrugation process which produces a flexible seamless tube with annular corrugations. The corrugations are what gives the conduit it's strong crush and impact resistance and excel lent flexibility properties. The internal corrugations are well rounded which facilitates easy wire insertion.

 

Material:

Halogen Free Nylon 6

 

Working Temperature:

-20C to 90C Intermitting to 150C

 

Standard Color:

Black. Other colors available upon request.

Page Contents


 

Type CLR-robotics

Very light weight and extremely flexible. This tubing is intended for applications requiring continuous, repeated flexible motion. Ideally suited for robotic equipment.

 

The Corrlok/PMAFIX System:

The Corrlok System offers designers and electricians many advantages over numerous other wiring products. It provides a very light weight, liquidtight, flexible raceway resistant to abrasion, sunlight, temperature extremes and many common chemicals. The specially formulated nylon compounds are self extinguishing and release no halogens or corrosive gases in fire situations.

 

Applications:

Corrlok conduits are defined in the National Electrical Code (ANSI/NFPA-70) under article 351-22 (3) for Liquidtight Flexible Nonmetallic Conduits. It's design is also referred to as type C. The Corrlok System is well suited for many electrical installa tions such as Industrial Control Equipment, Machine Tools and Plastic Molding/Extrusion machinery. Also used for wiring Printing Presses, Textile Machinery and Medical Equipment. The system also lends itself quite well to non-electrical applications suc h as protecting air-logic circuitry and Fiber Optics. The conduits can be extruded in other colors to differentiate between Electrical circuits and Fiber Optics.

Because the materials used are non-toxic and self extinguishing, Corrlok is a proven choice for situations where the potential for fire in confined, inhabited areas is a concern. Passenger rail vehicles are just one of the many such examples.

 

Construction:

Conduits of the Corrlok System are manufactured in a continuous extrusion/corrugation process which produces a flexible seamless tube with annular corrugations. The corrugations are what gives the conduit it's strong crush and impact resistance and excel lent flexibility properties. The internal corrugations are well rounded which facilitates easy wire insertion.

 

Material:

Halogen Free Nylon 12

 

Working Temperature:

-50C to 95C Intermitting to 150C

 

Standard Color:

Black. Other colors available upon request.

 

Tests Include:

-Over 10,000,000 bending cycles at 180 degree bends
-Over 4,000,000 bending cycles at 180 degree bends in two directions (reversed bends).
-Flammability rating UL94-V2

Fitting Pull-Out:

65 lbs. To be used only with Connectors of the Corrlok System.